5. CLI Commands
device: sensor: input
input
Use the input command to configure the input contacts of an E2MTHDI sensor.
Syntax
input {contact-1 | contact-2} alarm-level {normally_open | normally_closed}
input {contact-1 | contact-2} description <value>
value – Specifies a description for the input contact.
no input {contact-1 | contact-2} description <value>
value – Clears the description for the input contact.
Example
The following command sets “normally_open” as the contact-1 alarm level for sensor “E2MTHDI-123” connected to device
“PDU-Rack1”:
console> device (PDU-Rack1)> sensor (E2MTHDI-123)> input contact-1 alarm-level
normally_open
Update complete
The following command sets “Door 12-A” as the contact-2 description for sensor “E2MTHDI-123” connected to device “PDU-
Rack1”:
console> device (PDU-Rack1)> sensor (E2MTHDI-123)> input contact-2 description “Door
12-A”
Update complete
show input
Use the show input command to display the settings for the input contacts of the sensor.
Syntax
show input
Examples
The following command displays the input settings for sensor “E2MTHDI-123” connected to device “PDU-Rack1”:
console> device (PDU-Rack1)> sensor (E2MTHDI-123)> show input
NAME TYPE VALUE
------------------ -------------- ---------------------
Contact Input 1 Environment Open
..Alarm Level Normally Open
..Description Contact Input #1
Contact Input 2 Environment Open
..Alarm Level Normally Open
..Description Door 12-A