5. CLI Commands
battery transition count reset
Use the battery transition count reset command to clear the stored value identifying the number of times the device
transitioned from utility power to battery. Use the force option to execute the command without confirmation.
Syntax
battery transition count reset [force]
Example
The following command clears the stored battery transition count on device “UPS123”, with no confirmation:
console> device (UPS123)> battery transition count reset force
Execution complete
show battery
Use the show command, with optional keywords, to display details about the battery. To view all keywords applicable to the
battery, enter show battery [Tab][Tab].
Syntax
show battery [Tab][Tab]
Examples
The following command displays all battery-related show keywords for device “UPS123”:
console> device (UPS123)> show battery [Tab][Tab]
age fully rating transition
capacity high-critical replacement voltage
charge high-warning state
charged installed status
condition low temperature
count low-critical test
date low-warning threshold
discharged period tolerance
The following command displays all details about the battery associated with device “UPS123”:
console> device (UPS123)> show battery
NAME TYPE VALUE
----------------------- -------- -------------
Battery Temperature (C) Battery 35.0
Battery Temperature (F) Battery 95.0
Battery Age (Years) Battery 0.0
..Thresholds and Bounds
....High Warning 3.25
....High Critical 4.00
Battery Test Device Done and Passed
..Battery Test Date 3/31/2020
..Auto-Test Period 14 Days
..Initiate Battery Test
Battery Voltage (V) Battery 27.3