53
5. CLI Commands
device: bypass
bypass voltage
Use the bypass voltage command to set the lowest and highest acceptable input voltage for bypass operation. Expressed as
a percentage, the high limit is a positive integer and the low limit is a negative integer.
Syntax
bypass voltage {high-limit | low-limit} <integer-value>
• integer-value - Sets the value for the specified limit.
Examples
The following command sets the lower bypass voltage limit to -14 for device “UPS-123”:
console> device (UPS-123)> bypass voltage low-limit -14
Update complete
show bypass
Use the show bypass command to display all bypass values.
Syntax
show bypass [voltage | limit | line | count]
Examples
The following command displays all bypass values for device “UPS-123”:
console> device (UPS-123)> show bypass
NAME TYPE VALUE
---------------------- ------- ------
Bypass Limit Bypass
..Voltage Limit
....High Limit 10
....Low Limit -14
Hardware Conguration Device
..Bypass Line Count 0