Tripp Lite PDUMH30ATNET 2.9kW Single-Phase Switched Automatic Transfer Switch PDU, 2 120V L5-30P Inputs, 24 5-15/20R & 1 L5-30R Outputs, 2U, TAA

User’s Guide - Page 60

For PDUMH30ATNET.

PDF File Manual, 220 pages, Read Online | Download pdf file

PDUMH30ATNET photo
Loading ...
Loading ...
Loading ...
60
5. CLI Commands
Examples
The following command resets the recorded minimum and maximum voltage levels, on device “PDU-Rack1”, without
confirmation:
console> device (PDU-Rack1)> input voltage reset force
Execution complete
The following command sets 102 as the Low Critical input voltage threshold on device “PDU-Rack1”:
console> device (PDU-Rack1)> input voltage threshold low-critical 102
Update complete
show input
Use the show input command to display the device’s input metrics.
Syntax
show input [frequency | nominal | voltage]
Examples
The following command displays all input information for device “PDU-Rack1”:
console> device (PDU-Rack1)> show input
NAME TYPE VALUE
---------------------- ------- -------
Input Voltage (V) Input 120.9
..Recorded High/Low
....Minimum (V) 118.5
...Maximum (V) 121.6
Nominal Input Voltage (V) Input 120
High Critical 138
High Warning 132
Low Critical 102
Low Warning 108
device: last-reason
last-reason
Use the last-reason command to reset the recorded reason for the specified event. Upon entering the command, a prompt
will appear to confirm the action. Use the force option to execute the command without confirmation.
Syntax
last-reason {ac-failure | shutdown} reset [force]
Examples
The following command resets the last recorded AC failure reason, for device “UPS123”, with no confirmation:
console> device (UPS123)> last-reason ac-failure reset force
Execution complete
Loading ...
Loading ...
Loading ...