46
5. CLI Commands
device: asset-tag
asset-tag
Use the asset-tag command to optionally enter an asset identifier for the device. Use the no form of this command to clear
the entry.
Syntax
asset-tag <tag>
no asset-tag
tag – Specifies an identity for the device. If spaces are required, bookend the name in quotation marks (“).
Example
The following command assigns “IT123ZZ” as the asset tag for device “PDU-Rack1”:
console> device (PDU-Rack1)> asset-tag IT123ZZ
Update complete
show asset-tag
Use the show asset-tag command to display the identifier entered for the device.
Syntax
show asset-tag
Examples
The following command displays the asset tag for device “PDU-Rack1”:
console> device (PDU-Rack1)> show asset-tag
IT123ZZ
device: auto-restart
auto-restart low-voltage
Use the auto-restart low-voltage command to set whether a low-voltage event will cause the device to automatically restart.
Syntax
auto-restart low-voltage enable
no auto-restart low-voltage enable
Examples
The following command configures device “UPS-123” not to auto-restart if a low-voltage event occurs:
console> device (UPS-123)> no auto-restart low-voltage enable
Update complete