Tripp Lite PDUMH30ATNET 2.9kW Single-Phase Switched Automatic Transfer Switch PDU, 2 120V L5-30P Inputs, 24 5-15/20R & 1 L5-30R Outputs, 2U, TAA

User’s Guide - Page 55

For PDUMH30ATNET.

PDF File Manual, 220 pages, Read Online | Download pdf file

PDUMH30ATNET photo
Loading ...
Loading ...
Loading ...
55
5. CLI Commands
show date-installed
Use the show date-installed command to display the entered installation date.
Syntax
show date-installed
Examples
The following command displays the installation date entered for device “PDU-Rack1”:
console> device (PDU-Rack1)> show date-installed
10/16/2020
device: db9
db9 input
Use the db9 input command to set the input action when pins 3 and 9 of the DB9 port are shorted.
Syntax
db9 input 3-9 {shutdown_(default) | output_off | reboot | output_on | power_toggle}
Example
The following command sets Output Off as the DB9 port input action for device “UPS123”:
console> device (UPS123)> db9 input 3-9 output_o
Update complete
db9 output
Use the db9 output command to set the condition signaled by the UPS when pins 1 and 5 or pins 8 and 5 of the DB9 port
are shorted.
Syntax
db9 output 1-5 {on_battery_(default) | on_bypass | output_on | low_battery}
db9 output 8-5 {on_battery | on_bypass | output_on | low_battery_(default)}
Example
The following command sets Output On as the condition signalled by device “UPS123” when pins 8 and 5 of the DB9 port are
shorted:
console> device (UPS123)> db9 output 8-5 output_on
Update complete
Loading ...
Loading ...
Loading ...