5. CLI Commands
show on-battery
Use the show on-battery command to display the timed shutdown state and value.
Syntax
show on-battery [shutdown-seconds | shutdown-status]
Examples
The following command displays the timed shutdown settings for device “UPS123”:
console> device (UPS123)> show on-battery
NAME TYPE VALUE
---------------------------- -------- ---------
Seconds on Battery (Seconds) Battery 0
..Timed Shutdown Seconds 60
..Timed Shutdown Status Enabled
device: output
output
Use the output command to display the device’s output metrics and to configure output threshold settings. Output parameters
vary by device; use keywords to identify applicable output parameters. When the reset command is issued, a prompt will
appear to confirm the action. Use the force option to execute the reset without confirmation.
Syntax
output current reset [force]
output current {phase-1 | phase-2 | phase-3} reset [force]
output voltage rating {100 | 110 | 115 | 120 | 127 | 200 | 208 | 220 | 230 | 240}
output voltage threshold {low-critical | low-warning | high-warning | high-critical} <decimal-value>
output current threshold {low-warning | high-warning | high critical} <decimal-value>
output current {phase-1 | phase-2 | phase-3} threshold {low-warning | high-warning | high critical} <decimal-
value>
output load threshold high-critical <decimal-value>
output voltage threshold tolerance <decimal-value>
output utilization threshold tolerance <integer-value>
output utilization threshold high-critical <decimal-value>
integer-value – Specifies the numerical value for the output utilization threshold tolerance.
decimal-value – Specifies the numerical value for the specified threshold or tolerance.
Example
The following command resets the recorded minimum and maximum current levels, on device “PDU-Rack1”, without
confirmation:
console> device (PDU-Rack1)> output current reset force
Execution complete
The following command sets 102 as the Low Critical output voltage threshold on device “PDU-Rack1”:
console> device (PDU-Rack1)> output voltage threshold low-critical 102
Update complete