![](https://files.manualsfile.com/26308424-pdumh30atnet/bg32.png)
50
5. CLI Commands
battery test period
Use the battery test period command to configure auto-test of the battery (if supported by the device). Note that the
available period choices will vary by UPS model.
Syntax
battery test period {disabled | monthly | quarterly | semi-annually}
Example
The following command configures auto-test of the battery every quarter on device “UPS123”:
console> device (UPS123)> battery test period quarterly
Update complete
battery test start
Use the battery test start command to perform an on-demand battery test (if supported by the device). On executing this
command, a prompt will appear to confirm the action. Use the force option to execute the command without confirmation.
Syntax
battery test start [force]
Example
The following command initiates a battery test on device “UPS123”:
console> device (UPS123)> battery test start
Are you sure? Type “yes” to proceed: yes
Execution complete
battery threshold capacity tolerance
Use the battery threshold capacity tolerance command to set the margin which must be exceeded in order to re-trigger a
threshold event.
Syntax
battery threshold capacity tolerance <integer-value>
• integer-value - Specifies the tolerance value, as a percentage.
Example
The following command sets the battery threshold capacity tolerance at 5% for device “UPS123”:
console> device (UPS123)> battery threshold capacity tolerance 5
Update complete