5. CLI Commands
show energy saving setting
Use the show energy saving setting command to display the Energy Savings setting for the device.
Syntax
show energy saving setting
Examples
The following command displays the Energy Saving setting for device “UPS123”:
console> device (UPS123)> show energy saving setting
NAME TYPE VALUE
----------------- ------- ------
Hardware Features Device
..Energy Saving 15
device: fault
fault action
Use the fault action command to set the behavior of the UPS when a fault condition occurs. The bypass option maintains AC
output (so long as input voltage is within bypass high/low limits). The standby option causes the UPS to turn off AC output in
response to fault conditions.
Syntax
fault action {go_to_bypass | go_to_standby}
Examples
The following command configures device “UPS123” to maintain AC output if a fault condition occurs:
console> device (UPS123)> fault action go_to_bypass
Update complete
show fault action
Use the show fault action command to display the setting of how the device will behave when a fault condition occurs.
Syntax
show fault action
Examples
The following command displays the Fault Action setting for device “UPS123”:
console> device (UPS123)> show fault action
NAME TYPE VALUE
------------------ -------- ---------
Hardware Features Device
..Fault Action Go to Bypass