103
5. CLI Commands
show event
Use the show event command to display a summary table of all events or the details of a specified event entry. Note that the
list of events will vary by device type and model.
Syntax
show event [<event-name>]
event-name – Specifies the entry for which event details are to be displayed.
Examples
The following command displays a summary table of all events supported by the device (a basic UPS, in this example):
console> show event
NAME SEVERITY STATUS SOURCE AUTO-ACK
--------------------------------------------- ------- -------- ---------
Contact Input 1 In Alarm critical enabled Sensor1 enabled
Contact Input 2 In Alarm critical enabled Sensor1 enabled
Communications Lost information disabled Sensor1 disabled
Humidity Beyond Limits critical enabled Sensor1 enabled
Temperature Beyond Limits critical enabled Sensor1 enabled
Battery Age Above Threshold information enabled UPS123 enabled
Battery Low critical enabled UPS123 disabled
Communications Lost critical enabled UPS123 enabled
Event ABC warning enabled UPS123 disabled
Load 01 O warning enabled UPS123 enabled
Load 02 O warning enabled UPS123 enabled
Load Level Above Threshold warning enabled UPS123 enabled
Loads Not All On warning enabled UPS123 enabled
NTP Watchdog NTP Probe Failed warning enabled UPS123 enabled
On Battery critical enabled UPS123 enabled
Output O warning enabled UPS123 enabled
Overload critical enabled UPS123 disabled
Ping Watchdog Ping Probe Failed warning enabled UPS123 enabled
Self Test Failed warning enabled UPS123 enabled
Temperature High critical enabled UPS123 disabled
The following command displays the settings for event “Communications Lost”:
console> show event “Communications Lost”
NAME SEVERITY STATUS SOURCE AUTO-ACK LOGGING
---------------------- --------- ------- -------- --------- --------
Communications Lost information disabled Sensor1 disabled disabled
Communications Lost critical enabled UPS123 enabled disabled