5. CLI Commands
show humidity
Use the show humidity command to display a summary of humidity threshold settings.
Syntax
show humidity
Examples
The following command displays a summary of humidity threshold settings for sensor “E2MTHDI”, associated with device
“PDU123”:
console> device (PDU123)> sensor (E2MTHDI)> show humidity
NAME TYPE VALUE
------------------------ ----------- --------------
Hardware Conguration Device
..Humidity Supported Yes
Humidity (%) Environment 18
..Thresholds and Bounds
....Low Critical 5
....High Critical 45
....Tolerance 0
device: sensor: id
id
Use the id command to optionally set a numeric identifier for the sensor. Use the no form of this command to clear the entry.
Syntax
id <id>
id – Specifies a numerical identifier for the sensor (Range: 0-65535).
Example
The following command sets “12345” as the numerical identifier for sensor “E2MT1” connected to device “PDU-Rack1”:
console> device (PDU-Rack1)> sensor (E2MTD1)> id 12345
Update complete
show id
Use the show id command to display the identifier entered for the sensor.
Syntax
show id
Examples
The following command displays the numerical identifier for sensor “E2MT1” connected to device “PDU-Rack1”:
console> device (PDU-Rack1)> sensor (E2MTD1)> show id
12345