2 Parameters
2.2 List of parameters
SINAMICS G120C
92 List Manual (LH13), 04/2014, A5E33840768B AA
Note: Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
Description: Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p1055, p1056
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switch-on inhibit is acknowledged.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For drives with closed-loop speed control (p1300 = 20), the following applies:
- BI: p0840 = 0 signal: OFF1 (braking with the ramp-function generator, then pulse suppression and switch-on inhibit)
- BI: p0840 = 0/1 signal: ON (pulses can be enabled)
Description: Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p1055, p1056
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switch-on inhibit is acknowledged.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For drives with closed-loop speed control (p1300 = 20), the following applies:
- BI: p0840 = 0 signal: OFF1 (braking with the ramp-function generator, then pulse suppression and switch-on inhibit)
- BI: p0840 = 0/1 signal: ON (pulses can be enabled)
p0840[0...n] BI: ON / OFF (OFF1) / ON / OFF (OFF1)
G120C_CAN
G120C_USS
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 2610, 8720,
8820, 8920
Min Max Factory setting
- - [0] 722.0
[1] 0
p0840[0...n] BI: ON / OFF (OFF1) / ON / OFF (OFF1)
G120C_DP
G120C_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 2610, 8720,
8820, 8920
Min Max Factory setting
- - [0] 2090.0
[1] 0