SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
91
2 Parameters
2.2 List of parameters
Note: If the motor numbers are identical, the same thermal motor model is used for calculation after data set changeover.
If different motor numbers are used, different models are also used for calculating (the inactive motor cools down in
each case).
Description: Displays the status word for the drive data set changeover.
Note: Re bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
Re bit 04:
A data set changeover is only carried out when the armature short circuit is not activated.
Re bit 05:
A data set changeover is only carried out when pole position identification is not running.
Re bit 07:
A data set changeover is only carried out when rotating measurement is not running.
Re bit 08:
A data set changeover is only carried out when motor data identification is not running.
Description: Displays the command data set (CDS) selected via the binector input.
Dependency: Refer to: r0050, p0810
Note: Command data sets are selected via binector input p0810 and following.
The currently effective command data set is displayed in r0050.
Description: Displays the drive data set (DDS) selected via the binector input.
Dependency: Refer to: r0051, p0820
r0835.2...8 CO/BO: Data set changeover status word / DDS_ZSW
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8575
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
02 Internal parameter calculation active Yes No -
04 Armature short circuit active Yes No -
05 Identification running Yes No -
07 Rotating measurement running Yes No -
08 Motor data identification running Yes No -
r0836.0...1 CO/BO: Command Data Set CDS selected / CDS selected
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8560
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS select. bit 0 ON OFF -
01 CDS select. bit 1 ON OFF -
r0837.0 CO/BO: Drive Data Set DDS selected / DDS selected
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8565
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS select. bit 0 ON OFF -