2 Parameters
2.2 List of parameters
SINAMICS G120C
218 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Sets the type of technology controller.
Value: 0: D component in the actual value signal
1: D component in the fault signal
Description: Sets the signal source for the actual value of the technology controller.
Description: Sets the time constant for the actual value filter (PT1) of the technology controller.
Description: Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
Description: Sets the upper limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Notice: If the actual value exceeds this upper limit, this results in fault F07426.
Description: Sets the lower limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
p2263 Technology controller type / Tec_ctrl type
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0 1 0
p2264[0...n] CI: Technology controller actual value / Tec_ctrl act val
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2265 Technology controller actual value filter time constant / Tec_ctrl act T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]
p2267 Technology controller upper limit actual value / Tec_ctrl u_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2268 Technology controller lower limit actual value / Tec_ctrl l_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]