SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
169
2 Parameters
2.2 List of parameters
Description: Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Dependency: Refer to: p0287
Note: If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
Re bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), it is not repeated.
Re bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
Description: Sets the configuration for the motor data identification.
p1901 Test pulse evaluation configuration / Test puls config
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Phase short-circuit test pulse active Yes No -
01 Ground fault detection test pulse active Yes No -
02 Test pulse at each pulse enable Yes No -
p1909[0...n] Motor data identification control word / MotID STW
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0000 0000 0000 0000 0000
0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no
measurement
Yes No -
02 Rotor time constant estimate no
measurement
Yes No -
03 Leakage inductance estimate no
measurement
Yes No -
05 Determine Tr and Lsig evaluation in the time
range
Yes No -
06 Activate vibration damping Yes No -
07 De-activate vibration detection Yes No -
11 De-activate pulse measurement Lq Ld Yes No -
12 De-activate rotor resistance Rr
measurement
Yes No -
14 De-activate valve interlocking time
measurement
Yes No -
15 Determine only stator resistance, valve
voltage fault, dead time
Yes No -
16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter
calculation
Yes No -
18 After motID direct transition into operation Yes No -
19 After MotID automatically save results Yes No -
20 Estimate cable resistance Yes No -