3 Function diagrams
3.18 Data sets
SINAMICS G120C
450 List Manual (LH13), 04/2014, A5E33840768B AA
Fig. 3-112 8565 – Drive Data Sets (DDS)
- 8565 -
Function diagram
87654321
fp_8565_97_05.vsd
Data sets
SINAMICS G120C
07.04.2014 V4.7
Drive Data Sets (DDS)
DDS1
DDS0
<1>
<1>
A07530 "Drive data set does not exist"
A BICO interconnection to a parameter which is part of a drive data set always influences the currently effective data set.
(0)
DDS select., bit 0
p0820 [C]
DDS count
1 ... 2
p0180 (1)
DDS selected
r0837
r0837
DDS effective
r0051
r0051
Copy DDS, source
p0819[0] (0)
Copy DDS, start
p0819[2] (0)
Copy DDS, target
p0819[1] (1)
Note
Data sets can only be applied
and cleared when p0010 = 15
is set.