2 Parameters
2.2 List of parameters
SINAMICS G120C
150 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Sets the maximum output frequency for resonance damping for U/f control.
Resonance damping is inactive above this output frequency.
Dependency: Refer to: p1338
Note: For p1349 = 0, the changeover limit is automatically set to 95 % of the rated motor frequency - however, to a max. of
45 Hz.
Description: Sets the frequency setting value at the slip compensation output for starting up with motor holding brake.
Dependency: When setting p1351 > 0, then slip compensation is automatically activated (p1335 = 100 %).
Refer to: p1302, p1352
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: Connected with p1352 a value of 100% corresponds to the motor rated slip (r0330).
Description: Sets the signal source for the frequency setting value at the slip compensation output for starting up with motor
holding brake.
Dependency: Refer to: p1216
Note: A value of 100% corresponds to the motor rated slip (r0330).
The setting of the starting frequency begins after magnetizing (see p0346, r0056.4) and ends once the brake opening
time (p1216) has elapsed and the starting frequency (p1334) has been reached.
A setting value of zero means that no setting procedure will take place.
Description: Display and BICO output for the control word of the speed controller.
p1349[0...n] U/f mode resonance damping maximum frequency / Uf res_damp f_max
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]
p1351[0...n] CO: Motor holding brake starting frequency / Brake f_start
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
-300.00 [%] 300.00 [%] 0.00 [%]
p1352[0...n] CI: Motor holding brake starting frequency signal source / Brake f_start
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 6310
Min Max Factory setting
- - 1351[0]
r1406.4...15 CO/BO: Control word speed controller / STW n_ctrl
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 Hold speed controller I component Yes No 6040
05 Set speed controller I component Yes No 6040
11 Droop enable Yes No 6030
15 Set speed adaptation controller I
component
Yes No -