2 Parameters
2.1 Overview of parameters
SINAMICS G120C
16 List Manual (LH13), 04/2014, A5E33840768B AA
Data type
The information on the data type can consist of the following two items (separated by a slash):
• First item
Data type of the parameter.
• Second item (for binector or connector input only)
Data type of the signal source to be interconnected (binector-/connector output).
Parameters can have the following data types:
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source), the following combinations are possible when creating BICO
interconnections:
• Integer8 I8 8-bit integer number
• Integer16 I16 16-bit integer number
• Integer32 I32 32-bit integer number
• Unsigned8 U8 8 bits without sign
• Unsigned16 U16 16 bits without sign
• Unsigned32 U32 32 bits without sign
• FloatingPoint32 Float 32-bit floating point number
Table 2-2 Possible combinations of BICO interconnections
BICO input parameter
CI parameter BI parameter
BICO output parameter Unsigned32 /
Integer16
Unsigned32 /
Integer32
Unsigned32 /
FloatingPoint32
Unsigned32 /
Binary
CO: Unsigned8 x x – –
CO: Unsigned16 x x – –
CO: Unsigned32 x x – –
CO: Integer16 x x r2050 –
CO: Integer32 x x r2060 –
CO: FloatingPoint32 x x x –
BO: Unsigned8 – – – x
BO: Unsigned16 – – – x
BO: Unsigned32 – – – x
BO: Integer16 – – – x
BO: Integer32 – – – x
BO: FloatingPoint32 – – – –
Legend: x :
–:
rxxxx:
BICO interconnection permitted
BICO interconnection not permitted
BICO interconnection is only permitted for the specified CO parameters