SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
297
2 Parameters
2.2 List of parameters
Re bit 18:
When the bit is set, STO is selected via PROFIsafe.
Description: Displays the checksum for the Safety Integrated parameters checked using checksums on processor 2 (actual
checksum).
Dependency: Refer to: r9798, p9899
Description: Sets the checksum for the Safety Integrated parameters checked using checksums on processor 2 (setpoint
checksum).
Dependency: Refer to: p9799, r9898
Description: Displays the system utilization.
If the utilization is greater than 100%, fault F01054 is output.
Index: [0] = Reserved
[1] = Computing time utilization
[2] = Reserved
[3] = Reserved
[4] = Reserved
[5] = Largest total utilization
[6] = Reserved
[7] = Reserved
Note: Re index 1:
The value shows the total computing time load of the system.
Re index 5:
The total utilization is determined using all sampling times used. The largest total utilization is mapped here. The
sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
Description: Sets the telegram number for PROFIsafe.
r9898 SI actual checksum SI parameters (processor 2) / SI act_chksm P2
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
- - -
p9899 SI setpoint checksum SI parameters (processor 2) / SI setp_chksm P2
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
r9976[0...7] System utilization / Sys util
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [%] - [%] - [%]
p60022 PROFIsafe telegram selection / Ps telegram_sel
G120C_DP
G120C_PN
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 998 998