SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
153
2 Parameters
2.2 List of parameters
Description: Display and connector output for the torque setpoint at the output of the I speed controller.
Description: Display and connector output for the parameterized total moment of inertia.
The value is calculated with ((p0341 * p0342) * p1496).
Description: Sets the scaling for the acceleration pre-control of the speed/velocity controller.
Dependency: Refer to: p0341, p0342
Warning: The acceleration precontrol r1518 is kept at the old value if the ramp-function generator tracking (r1199.5) is active or
the ramp-function generator output is set (r1199.3). This is used to avoid torque peaks. Depending on the application,
it may therefore be necessary to disable the ramp-function generator tracking (p1145 = 0) or the acceleration
precontrol (p1496 = 0).
The acceleration precontrol is set to zero, if the Vdc control is active (r0056.14/15).
Note: The parameter is set to 100% by the rotating measurement (refer to p1960).
The acceleration pre-control may not be used if the speed setpoint manifests significant ripple (e.g. analog setpoint)
and the rounding-off in the speed ramp-function generator is disabled.
We also recommend that the pre-control mode is not used if there is gearbox backlash.
Description: Sets the load moment of inertia.
Note: (p0341 * p0342) + p1498 influence the speed/torque pre-control in encoderless operation.
r1482 CO: Speed controller I torque output / n_ctrl I-M_outp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dyn. index: -
Units group: 7_1 Unit selection: p0505 Func. diagram: 5040, 5042, 5210,
6030, 6040
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r1493 CO: Moment of inertia total, scaled / M_mom inert tot_sc
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: 25_1 Unit selection: p0100 Func. diagram: 6031
Min Max Factory setting
- [kgm²] - [kgm²] - [kgm²]
p1496[0...n] Acceleration pre-control scaling / a_prectrl scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6020, 6031
Min Max Factory setting
0.0 [%] 10000.0 [%] 0.0 [%]
p1498[0...n] Load moment of inertia / Load M_inertia
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 25_1 Unit selection: p0100 Func. diagram: 5042, 5210
Min Max Factory setting
0.00000 [kgm²] 100000.00000 [kgm²] 0.00000 [kgm²]