SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
201
2 Parameters
2.2 List of parameters
Description: Displays the system runtime in milliseconds when the alarm was cleared.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2134
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description: Selects the faults for which the acknowledge mode is to be changed
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description: Sets the acknowledge mode for selected fault.
Value: 1: Acknowledgment only using POWER ON
2: Ack IMMEDIATELY after the fault cause has been removed
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
Notice: It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
Description: Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
r2125[0...63] Alarm time removed in milliseconds / t_alarm res ms
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8050, 8065
Min Max Factory setting
- [ms] - [ms] - [ms]
p2126[0...19] Change acknowledge mode fault number / Chng ackn F_no
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8050, 8075
Min Max Factory setting
0 65535 0
p2127[0...19] Change acknowledge mode mode / Chng ackn mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8050, 8075
Min Max Factory setting
1 2 1
p2128[0...15] Faults/alarms trigger selection / F/A trigger sel
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8050, 8070
Min Max Factory setting
0 65535 0