2 Parameters
2.2 List of parameters
SINAMICS G120C
160 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
Description: Sets the smoothing time for the flux setpoint.
Description: Sets the scaling of the pre-control characteristic for the start of field weakening.
For values above 100 % and for partial load situations, the field weakening starts at higher speeds.
Note: If the start of field weakening is shifted to lower speeds, then the voltage reserve is increased for partial load
situations.
If the start of field weakening is shifted to higher speeds, the voltage reserve is appropriately reduced so that for fast
load changes, it can be expected that this will have a negative impact on the dynamic performance.
Description: Sets the proportional gain for the flux controller.
Note: The value is automatically pre-assigned dependent on the motor when the drive system is first commissioned.
When calculating controller parameters (p0340 = 4), this value is re-calculated.
p1580[0...n] Efficiency optimization / Efficiency opt.
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722
Min Max Factory setting
0 [%] 100 [%] 0 [%]
p1582[0...n] Flux setpoint smoothing time / Flux setp T_smth
Access level: 4 Calculated: p0340 = 1,3 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6722, 6724
Min Max Factory setting
4 [ms] 5000 [ms] 15 [ms]
p1586[0...n] Field weakening characteristic scaling / Field weak scal
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
80.0 [%] 120.0 [%] 100.0 [%]
p1590[0...n] Flux controller P gain / Flux controller Kp
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
0.0 999999.0 10.0