User Manual - Page 413

For G120C.

Loading ...
Loading ...
Loading ...
SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
413
3 Function diagrams
3.13 Vector control
Fig. 3-80 6630 – Upper/lower torque limit
- 6630 -
Function diagram
87654321
fp_6630_97_05.vsd
Vector control
SINAMICS G120C
07.04.2014 V4.7
Upper/lower torque limit
M
n
43
M
n
21
[6640.1]
[6640.1]
<1>
<1>
!
Upper torque limit
Lower torque limit
Danger: Negative values at <1>
positive values at <2>
represent a minimum torque for the other torque direction and can cause the motor to accelerate uncontrollably.
M_max upper
-1000000.00 ... 20000000.00 [Nm]
p1520 [D] (0.00)
M_max upper
(1520[0])
p1522 [C]
M_max lower
(1521[0])
p1523 [C]
<2>
<2>
!
!
M_max lower
-20000000.00 ... 1000000.00 [Nm]
p1521 [D] (0.00)
M_max lower scal
-2000.0 ... 2000.0 [%]
p1525 [D] (100.0)
M_max upper scal
-2000.0 ... 2000.0 [%]
p1524 [D] (100.0)
r1526
M_max up w/o offs [Nm]
r1527
M_max low w/o offs [Nm]
Loading ...
Loading ...
Loading ...