2 Parameters
2.2 List of parameters
SINAMICS G120C
48 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Displays the rated line supply voltage of the power unit.
r0208 = 400 : 380 - 480 V +/-10 %
r0208 = 500 : 500 - 600 V +/-10 %
r0208 = 690 : 660 - 690 V +/-10 %
Description: Displays the maximum output current of the power unit.
Index: [0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency: Refer to: p0205
Description: Sets the drive unit supply voltage (rms value of the phase-to-phase line supply voltage).
Dependency: Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller (r1242, r1282) are then directly determined using p0210.
Notice: If, in the switched-off state (pulse inhibit), the supply voltage is higher than the entered value, the Vdc controller may
be automatically de-activated in some cases to prevent the motor from accelerating the next time the system is
switched on. In this case, an appropriate alarm A07401 is output.
Note: Setting ranges for p0210 as a function of the rated power unit voltage:
U_rated = 230 V:
- p0210 = 200 ... 240 V
U_rated = 400 V:
- p0210 = 380 ... 480 V
U_rated = 690 V:
- p0210 = 660 ... 690 V
Description: Sets the braking power of the connected braking resistor.
Dependency: Refer to: p1240, p1280, p1531
r0208 Rated power unit line supply voltage / PU U_rated
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0209[0...4] Power unit maximum current / PU I_max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8750, 8850, 8950
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p0210 Drive unit line supply voltage / V_connect
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(2), T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 [V] 63000 [V] 400 [V]
p0219 Braking resistor braking power / R_brake P_brake
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(1, 2), T Scaling: - Dyn. index: -
Units group: 14_6 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
0.00 [kW] 20000.00 [kW] 0.00 [kW]