2 Parameters
2.2 List of parameters
SINAMICS G120C
288 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Displays the time remaining before dynamization and testing of the safety shutdown paths (forced checking
procedure).
Description: CRC via Node Identifier of the Control Unit.
Note: CU: Control Unit
Description: CRC via the Node Identifier of a Power Module.
Note: PM: Power Module
Description: Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
Value: 0: [00 hex] Copy function ended
29: [1D hex] Start copy function node identifier
87: [57 hex] Start copy function SI parameters
208: [D0 hex] Start copy function SI basic parameters
Dependency: Refer to: r3996
Notice: When the parameters are copied, short-term communication interruptions may occur.
Note: Re value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
Re value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9610 --> 9810, p9650 --> p9850, p9651 --> p9851
r9660 SI forced checking procedure remaining time / SI frc chk remain
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [h] - [h] - [h]
r9670 SI module identification Control Unit / Module ID CU
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4294967295 -
r9672 SI module identifier Power Module / Module ID PM
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 4294967295 -
p9700 SI copy function / SI copy function
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95), U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00D0 hex 0000 hex