SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
117
2 Parameters
2.2 List of parameters
Dependency: Refer to: p0840, p1059
Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
Description: Sets the signal source for jog 2.
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p0840, p1059
Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
Description: Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: Refer to: p1071, r1073, r1078
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1056[0...n] BI: Jog bit 1 / Jog bit 1
G120C_DP
G120C_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 3030
Min Max Factory setting
- - [0] 0
[1] 722.1
p1058[0...n] Jog 1 speed setpoint / Jog 1 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3001, 3030
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 150.000 [rpm]
p1059[0...n] Jog 2 speed setpoint / Jog 2 n_set
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3001, 3030
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] -150.000 [rpm]
p1070[0...n] CI: Main setpoint / Main setpoint
G120C_CAN
G120C_USS
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2000 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3001, 3030
Min Max Factory setting
- - [0] 755[0]
[1] 0