SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
185
2 Parameters
2.2 List of parameters
Description: Diagnostics display for the PROFIBUS interface.
Index: [0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
Description: Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency: Refer to: p0918
Notice: The display is updated after switching on, and not cyclically.
Description: Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
Dependency: Refer to: r2050
Notice: Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Description: Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
r2055[0...2] PROFIBUS diagnostics standard / PB diag standard
G120C_DP Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
r2057 PROFIBUS address switch diagnostics / PB addr_sw diag
G120C_DP Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2410
Min Max Factory setting
- - -
r2060[0...10] CO: PROFIdrive PZD receive double word / PZD recv DW
Access level: 3 Calculated: - Data type: Integer32
Can be changed: - Scaling: 4000H Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2440, 2468
Min Max Factory setting
- - -
p2061[0...12] CI: PROFIBUS PZD send double word / PZD send DW
Access level: 3 Calculated: - Data type: U32 / Integer32
Can be changed: U, T Scaling: 4000H Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2470
Min Max Factory setting
- - 0
Loading ...
Loading ...
Loading ...