SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
81
2 Parameters
2.2 List of parameters
Description: Determines the width of the dead zone at the analog input.
Analog input type unipolar (e.g. 0 ... +10 V):
The dead zone starts with the characteristic value x1/y1 (p0757/p0758).
Analog input type bipolar (e.g. -10 V ... +10 V):
The dead zone is located at the symmetrical center between characteristic value x1/y1 (p0757/p0758) and x2/y2
(p0759/p0760). The set value doubles the dead zone.
Index: [0] = AI0 (T. 3/4)
[1] = AI1 (T. 10/11)
Note: AI: Analog Input
T: Terminal
Description: Sets the signal source for the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
Description: Displays the actual referred output value of the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Note: AO: Analog Output
T: Terminal
Description: Displays the actual output voltage or output current at the analog outputs.
Index: [0] = AO0 (T 12/13)
[1] = AO1 (T 26/27)
Dependency: Refer to: p0776
p0764[0...1] CU analog inputs dead zone / CU AI dead zone
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2251
Min Max Factory setting
0.000 [V] 20.000 [V] 0.000 [V]
p0771[0...1] CI: CU analog outputs signal source / CU AO S_src
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2261
Min Max Factory setting
- - [0] 21[0]
[1] 27[0]
r0772[0...1] CU analog outputs output value currently referred / CU AO outp act ref
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
- [%] - [%] - [%]
r0774[0...1] CU analog outputs output voltage/current actual / CU AO U/I_outp
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2001 Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9572
Min Max Factory setting
- - -