User Manual - Page 283

For G120C.

Loading ...
Loading ...
Loading ...
SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
283
2 Parameters
2.2 List of parameters
Note: A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Setting the USB functionality.
Value: 1: USS commissioning via the virtual COM port
2: Only memory access
3: USB commissioning and memory access
Note: COMM: Commissioning.
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Setting and display when memory card is "removed safely".
Procedure:
Setting p9400 = 2 results in a value of 3
--> The memory card can be removed safely. After removal the value sets itself to 0 automatically.
Setting p9400 = 2 results in a value of 100
--> The memory card cannot be removed safely. Removal may destroy the file system on the memory card. It may be
necessary to set p9400 = 2 again.
Value: 0: No memory card inserted
1: Memory card inserted
2: Request "safe removal" of the memory card
3: "Safe removal" possible
100: "Safe removal" not possible due to access
Dependency: Refer to: r9401
Notice: Removing the memory card without a request (p9400 = 2) and confirmation (p9400 = 3) may destroy the file system
on the memory card. The memory card will then no longer work properly and must be replaced.
Note: The status when the memory card is being "removed safely" is shown in r9401.
Re value = 0, 1, 3, 100:
These values can only be displayed, not set.
Description: Displays the status of the memory card.
Dependency: Refer to: p9400
p8999 USB functionality / USB Fct
Access level: 4 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 3 3
p9400 Safely remove memory card / Mem_card rem
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 100 0
r9401 Safely remove memory card status / Mem_card rem stat
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Memory card inserted Yes No -
01 Memory card activated Yes No -
02 SIEMENS memory card Yes No -
03 Memory card as USB data storage medium
from the PC used
Yes No -
Loading ...
Loading ...
Loading ...