2 Parameters
2.2 List of parameters
SINAMICS G120C
102 List Manual (LH13), 04/2014, A5E33840768B AA
Note: Example:
r0964[0] = 42 --> SIEMENS
r0964[1] = device type, see below
r0964[2] = 403 --> first part of the firmware version V04.03 (for second part, refer to index 6)
r0964[3] = 2010 --> year 2010
r0964[4] = 1705 --> 17th of May
r0964[5] = 2 --> 2 drive objects
r0964[6] = 200 --> second part, firmware version (complete version: V04.03.02.00)
Device type:
r0964[1] = 6510 --> SINAMICS G120C_DP
r0964[1] = 6511 --> SINAMICS G120C_PN
r0964[1] = 6512 --> SINAMICS G120C_CAN
r0964[1] = 6513 --> SINAMICS G120C_USS/MB
Description: Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note: When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
Description: Displays the system runtime in ms since the last POWER ON.
Note: The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
Description: The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
When downloading settings 10, 11, 12, the buffer memory mode is automatically deactivated (p0014 = 0).
Value: 0: Inactive
1: Start a parameter reset
3: Start download of volatile parameters from RAM
5: Starts a safety parameter reset
10: Start loading the parameters saved with p0971=10
11: Start loading the parameters saved with p0971=11
12: Start loading the parameters saved with p0971=12
r0965 PROFIdrive profile number / PD profile number
G120C_DP
G120C_PN
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
p0969 System runtime relative / t_System relative
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8050, 8060
Min Max Factory setting
0 [ms] 4294967295 [ms] 0 [ms]
p0970 Reset drive parameters / Drive par reset
Access level: 1 Calculated: - Data type: Unsigned16
Can be changed: C(1, 30) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 300 0