2 Parameters
2.2 List of parameters
Description: Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency: Refer to: p2230
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency: Refer to: r2250
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2248
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2247
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
p2240[0...n] Technology controller motorized potentiometer starting value / Tec_ctrl mop start
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7954
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
r2245 CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Units group: 9_1 Unit selection: p0595 Func. diagram: 7954
Min Max Factory setting
- [%] - [%] - [%]
p2247[0...n] Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 7954
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]
p2248[0...n] Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 7954
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]