User Manual - Page 76

For G120C.

Loading ...
Loading ...
Loading ...
2 Parameters
2.2 List of parameters
SINAMICS G120C
76 List Manual (LH13), 04/2014, A5E33840768B AA
Note: AI: Analog Input
DI: Digital Input
T: Terminal
Description: Sets the debounce time for digital inputs.
Note: The digital inputs are read in cyclically every 2 ms (DI 11, DI 12 every 4 ms).
To debounce the signals, the set debounce time is converted into integer multiple debounce clock cycles Tp (Tp =
p0724 / 2 ms).
DI: Digital Input
Description: Sets the signal source for terminal DO 0 (NO: T. 19 / NC: T. 18).
Recommend.: r0052.0 Ready for switching on
r0052.1 Ready for operation
r0052.2 Operation enabled
r0052.3 Fault present
r0052.4 Coast down active (OFF2)
r0052.5 Quick stop active (OFF3)
r0052.6 Switching on inhibited active
r0052.7 Alarm present
r0052.9 Control request
r0052.14 Motor rotates forwards
r0053.0 DC braking active
r0053.1 n_act > p2167 (n_off)
r0053.2 n_act <= p1080 (n_min)
r0053.3 I_act > p2170
r0053.4 n_act > p2155
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: DO: Digital Output
T: Terminal
Relay output: NO = normally open, NC = normally closed
Description: Sets the signal source for terminal DO 1 (NO: T. 21).
p0724 CU digital inputs debounce time / CU DI t_debounce
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [ms] 20.000 [ms] 4.000 [ms]
p0730 BI: CU signal source for terminal DO 0 / CU S_src DO 0
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2119, 2030, 2130
Min Max Factory setting
- - 52.3
p0731 BI: CU signal source for terminal DO 1 / CU S_src DO 1
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2119, 2030, 2130
Min Max Factory setting
- - 52.7
Loading ...
Loading ...
Loading ...