2 Parameters
2.2 List of parameters
SINAMICS G120C
280 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Displays the active subnet mask for the onboard PROFINET interface on the Control Unit.
Description: Displays the active DHCP mode for the onboard PROFINET interface on the Control Unit.
Notice: When the DHCP mode is active (parameter value greater than 0), PROFINET communication via this interface is no
longer possible! However, the interface can be used for commissioning tool such as STARTER or SCOUT.
Note: If value = 0:
DHCP deactivated.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
Description: Displays the MAC address for the onboard PROFINET interface on the Control Unit.
Description: Displays the PROFINET Device Access Point ID (DAP ID) for the onboard PROFINET interface.
The combination of device ID (r8909) and DAP ID uniquely identifies a PROFINET access point.
Note: List of the SINAMICS DAP IDs:
20007 hex: CBE20 V4.5
20008 hex: CBE20 V4.6
20107 hex: CU310-2 PN V4.5
20108 hex: CU310-2 PN V4.6
20307 hex: CU320-2 PN V4.5
20308 hex: CU320-2 PN V4.6
20407 hex: CU230P-2 PN /CU240x-2 PN V4.5
20408 hex: CU230P-2 PN /CU240x-2 PN /CU250S-2 PN /G110M PN V4.6
20507 hex: CU250D-2 PN V4.5
20508 hex: CU250D-2 PN V4.6
r8933[0...3] PN Subnet Mask of Station active / PN Subnet Mask act
G120C_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r8934 PN DHCP Mode active / PN DHCP Mode act
G120C_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r8935[0...5] PN MAC Address of Station / PN MAC of Station
G120C_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00FF hex -
r8939 PN DAP ID / PN DAP ID
G120C_PN Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Loading ...