2 Parameters
2.2 List of parameters
SINAMICS G120C
126 List Manual (LH13), 04/2014, A5E33840768B AA
Note: The ramp-up time is set in p1120.
Description: Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency: Refer to: p1121
Note: The ramp-down time is set in p1121.
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency: Refer to: r0054, p1141, p1142
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency: Refer to: r0054, p1141, p1142
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1139[0...n] CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
- - 1
p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
G120C_CAN
G120C_USS
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - 1
p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
G120C_DP
G120C_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501
Min Max Factory setting
- - [0] 2090.4
[1] 1
Loading ...
Loading ...
Loading ...