2 Parameters
2.2 List of parameters
SINAMICS G120C
152 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Display and connector output for the actual smoothed speed actual value of the speed control.
Description: Sets the smoothing time for the actual speed of the speed controller for encoderless closed-loop speed control.
Note: The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
Description: Sets the P gain for encoderless operation for the speed controller.
Note: The product p0341 x p0342 is taken into account when automatically calculating the speed controller (p0340 = 1, 3,
4).
Description: Set the integral time for encoderless operation for the speed controller.
Note: The integral component is stopped if the complete controller output or the sum of controller output and torque pre-
control reach the torque limit.
Description: Sets the signal source for the torque setting value when starting up with motor holding brake.
Dependency: .
Note: The setting of the integral output of the speed controller begins after magnetizing (see p0346, r0056 bit 4) and ends
at the end of the brake control opening time p1216. A setting value of zero means that no setting procedure will take
place.
If p1351 is used as a signal source for the torque setting value, the percentage value is interpreted in relation to the
rated torque (p2003).
r1445 CO: Actual speed smoothed / n_act smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 6040
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1452[0...n] Speed controller speed actual value smoothing time (sensorless) / n_C n_act T_s SL
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6020, 6040
Min Max Factory setting
0.00 [ms] 32000.00 [ms] 10.00 [ms]
p1470[0...n] Speed controller encoderless operation P-gain / n_ctrl SL Kp
Access level: 2 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6040, 6050
Min Max Factory setting
0.000 999999.000 0.300
p1472[0...n] Speed controller encoderless operation integral time / n_ctrl SL Tn
Access level: 2 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6040, 6050
Min Max Factory setting
0.0 [ms] 100000.0 [ms] 20.0 [ms]
p1475[0...n] CI: Speed controller torque setting value for motor holding brake / n_ctrl M_sv MHB
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 6040
Min Max Factory setting
- - 0