2 Parameters
2.2 List of parameters
Description: Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
Description: Displays the total effective setpoint.
The value indicates the sum of the effective main setpoint and supplementary setpoint.
Description: Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency: Refer to: p1106
Notice: The effective minimum speed is formed from p1080 and p1106.
Note: The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
Description: Sets the scaling for the maximum speed (p1082).
For a higher-level speed control, this scaling allows the maximum speed to be briefly exceeded.
Dependency: Refer to: p1082
Notice: Continuous operation above a scaling of 100 % is not permitted.
Description: Sets the highest possible speed.
Example:
Induction motor p0310 = 50 / 60 Hz without output filter and Blocksize power unit
p1082 <= 60 x 240 Hz / r0313 (vector control)
p1082 <= 60 x 550 Hz / r0313 (U/f control)
r1077 CO: Supplementary setpoint effective / Suppl setpoint eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 3030
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1078 CO: Total setpoint effective / Total setpoint eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 3030
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1080[0...n] Minimum speed / n_min
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C(1), T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3050, 8020
Min Max Factory setting
0.000 [rpm] 19500.000 [rpm] 0.000 [rpm]
p1081 Maximum speed scaling / n_max scal
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Units group: - Unit selection: - Func. diagram: 3050, 3095
Min Max Factory setting
100.00 [%] 105.00 [%] 100.00 [%]
p1082[0...n] Maximum speed / n_max
Access level: 1 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(1), T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: 3020, 3050, 3070
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 1500.000 [rpm]