2 Parameters
2.2 List of parameters
SINAMICS G120C
32 List Manual (LH13), 04/2014, A5E33840768B AA
Note: The value of -200 indicates that there is no measuring signal.
r0037[0]: Maximum value of the inverter temperatures (r0037[5...10]).
r0037[1]: Maximum value of the depletion layer temperatures (r0037[13...18]).
r0037[2]: Maximum value of the rectifier temperatures (r0037[11...12]).
The maximum value is the temperature of the hottest inverter, depletion layer, or rectifier.
r0037[2, 3, 6, 11, 14...18] is only relevant for chassis power units.
In the case of a fault, the particular shutdown threshold depends on the power unit, and cannot be read out.
Description: Displays the smoothed actual power factor. This refers to the electrical power of the basic fundamental signals at the
converter output terminals.
Notice: For infeed units, the following applies:
For active powers < 25 % of the rated power, this does not provide any useful information.
Note: Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
Description: Displays the energy values at the output terminals of the power unit.
Index: [0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency: Refer to: p0040
Note: Re index 0:
Sum of the energy drawn and energy that is fed back.
Description: Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency: Refer to: r0039
Description: Displays the saved energy referred to 100 operating hours.
r0038 Power factor smoothed / Cos phi smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 6799, 8850, 8950
Min Max Factory setting
- - -
r0039[0...2] Energy display / Energy displ
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [kWh] - [kWh] - [kWh]
p0040 Reset energy consumption display / Energy usage reset
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
r0041 Energy consumption saved / Energy cons saved
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [kWh] - [kWh] - [kWh]