2 Parameters
2.2 List of parameters
SINAMICS G120C
90 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency: Refer to: r0050, r0836
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description: Copies one Drive Data Set (DDS) into another.
Index: [0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Dependency: Refer to: r3996
Notice: When the drive data sets are copied, short-term communication interruptions may occur.
Note: Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, p0826, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the freely-assignable motor number for the drive data set changeover.
If the same motor is driven by different drive data sets, the same motor number must also be entered in these data
sets.
If the motor is also switched with the drive data set, different motor numbers must be used. In this case, the data set
can only be switched when the pulse inhibit is set.
p0810 BI: Command data set selection CDS bit 0 / CDS select., bit 0
G120C_DP
G120C_PN
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8560
Min Max Factory setting
- - 722.3
p0819[0...2] Copy Drive Data Set DDS / Copy DDS
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: C(15) Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 8565
Min Max Factory setting
0 1 0
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: C(15), T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 8565
Min Max Factory setting
- - 0
p0826[0...n] Motor changeover motor number / Mot_chng mot No.
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(3), T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0