2 Parameters
2.2 List of parameters
SINAMICS G120C
116 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Recommend.: Interconnect the signal with main setpoint (p1070).
Dependency: Refer to: p1070
Note: For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
suppress pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
Description: Sets the signal source for jog 1.
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p0840, p1058
Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
Description: Sets the signal source for jog 1.
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: Refer to: p0840, p1058
Notice: The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to power up can also be used to power down again.
Description: Sets the signal source for jog 2.
Recommend.: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
r1050 CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: 3_1 Unit selection: p0505 Func. diagram: 3001, 3020
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1055[0...n] BI: Jog bit 0 / Jog bit 0
G120C_CAN
G120C_USS
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 3030
Min Max Factory setting
- - 0
p1055[0...n] BI: Jog bit 0 / Jog bit 0
G120C_DP
G120C_PN
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 3030
Min Max Factory setting
- - [0] 0
[1] 722.0
p1056[0...n] BI: Jog bit 1 / Jog bit 1
G120C_CAN
G120C_USS
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 2501, 3030
Min Max Factory setting
- - 0