2 Parameters
2.2 List of parameters
SINAMICS G120C
50 List Manual (LH13), 04/2014, A5E33840768B AA
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note: When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
The parameter cannot be changed if the power unit has an internal sine-wave filter.
Description: Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
Refer to: p0230
Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined
SIEMENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside
the commissioning phase (p0010 = 0).
The parameter cannot be changed if the power unit has an internal sine-wave filter.
Description: Displays the internal resistance of the power unit (IGBT and line resistance).
Description: Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index: [0] = Threshold at which pre-charging starts
[1] = Threshold at which pre-charging stops
Dependency: Refer to: p1901
Note: This parameter is only relevant for chassis power units.
Description: Displays the actual maximum output current of the power unit taking into account derating factors.
p0234 Power unit sine-wave filter capacitance / PU sine filter C
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(2), U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [µF] 1000.000 [µF] 0.000 [µF]
r0238 Internal power unit resistance / PU R internal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0287[0...1] Ground fault monitoring thresholds / Gnd flt threshold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0 [%] 100.0 [%] [0] 6.0 [%]
[1] 16.0 [%]
r0289 CO: Maximum power unit output current / PU I_outp max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Arms] - [Arms] - [Arms]