SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
139
2 Parameters
2.2 List of parameters
Description: Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller.
Value: 0: Automatic detection inhibited
1: Automatic detection enabled
Description: Sets the time threshold for the Vdc_min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized.
Prerequisite: p1256 = 1
Notice: If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1240 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the event
of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
Description: Sets the response for the Vdc_min controller (kinetic buffering).
Value: 0: Buffer Vdc until undervoltage, n<p1257 -> F07405
1: Buff. Vdc until undervolt., n<p1257 -> F07405, t>p1255 -> F07406
Description: Sets the speed threshold for the Vdc-min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized .
Kinetic buffering is not started below the speed threshold.
Note: Exiting the Vdc_min control before reaching motor standstill prevents the regenerative braking current from
increasing significantly at low speeds, and after a pulse inhibit, means that the motor coasts down.
However, the maximum braking torque can be set via the appropriate torque limiting.
Description: Displays the actual output of the Vdc controller (DC link voltage controller)
p1254 Vdc_max controller automatic ON level detection / Vdc_max SenseOnLev
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 1
p1255[0...n] Vdc_min controller time threshold / Vdc_min t_thresh
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 1800.000 [s] 0.000 [s]
p1256[0...n] Vdc_min controller response (kinetic buffering) / Vdc_min response
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p1257[0...n] Vdc_min controller speed threshold / Vdc_min n_thresh
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 50.00 [rpm]
r1258 CO: Vdc controller output / Vdc_ctrl output
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dyn. index: -
Units group: 6_2 Unit selection: p0505 Func. diagram: 6220
Min Max Factory setting
- [Arms] - [Arms] - [Arms]