SINAMICS G120C
List Manual (LH13), 04/2014, A5E33840768B AA
59
2 Parameters
2.2 List of parameters
4: Calculation of controller parameters
5: Calculation of technological limits and threshold values
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
The following parameters are influenced using p0340:
p0340 = 1:
--> All of the parameters influenced for p0340 = 2, 3, 4, 5
--> p0341, p0342, p0344, p0640, p1082, p1231, p1232, p1349, p1611, p1726, p1909, p1959, p2000, p2001, p2002,
p2003, p3927, p3928
p0340 = 2:
--> p0350, p0354 ... p0360
--> p0625 (matching p0350)
p0340 = 3:
--> All of the parameters influenced for p0340 = 4, 5
--> p0346, p0347, p0622, p1320 ... p1327, p1582, p1755
p0340 = 4:
--> p1290, p1292, p1338, p1340, p1341, p1345, p1346, p1470, p1472, p1764, p1767
p0340 = 5:
--> p1037, p1038, p1520, p1521, p1530, p1531, p1802, p1803, p2390, p2392, p2393
Note: p0340 = 1 contains the calculations of p0340 = 2, 3, 4, 5.
p0340 = 2 calculates the motor parameters (p0350 ... p0360).
p0340 = 3 contains the calculations of p0340 = 4, 5.
p0340 = 4 only calculates the controller parameters.
p0340 = 5 only calculates the controller limits.
When quick commissioning is exited using p3900 > 0, p0340 is automatically set to 1.
At the end of the calculations, p0340 is automatically set to 0.
Description: Sets the motor moment of inertia (without load).
Dependency: IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
The parameter value is included, together with p0342, in the rated starting time of the motor.
Refer to: p0342, r0345
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
Description: Sets the ratio between the total moment of inertia/mass (load + motor) and the intrinsic motor moment of inertia/mass
(no load).
Dependency: This means that together with p0341, the rated starting (accelerating time) of the motor is calculated for a vector
drive.
Refer to: p0341, r0345, p1498
p0341[0...n] Motor moment of inertia / Mot M_mom of inert
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 25_1 Unit selection: p0100 Func. diagram: 5042, 5210, 6020,
6030, 6031
Min Max Factory setting
0.000000 [kgm²] 100000.000000 [kgm²] 0.000000 [kgm²]
p0342[0...n] Ratio between the total and motor moment of inertia / Mot MomInert Ratio
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 5042, 5210, 6020,
6030, 6031
Min Max Factory setting
1.000 10000.000 1.000