2 Parameters
2.2 List of parameters
SINAMICS G120C
166 List Manual (LH13), 04/2014, A5E33840768B AA
If a sine-wave filter is parameterized as output filter (p0230 = 3), then the pulse frequency cannot be set below the
minimum value required for the filter.
For operation with output reactors, the pulse frequency is limited to 4 kHz (see p0230).
If p1800 is changed during commissioning (p0010 > 0), then it is possible that the old value will no longer be able to
be set. The reason for this is that the dynamic limits of p1800 have been changed by a parameter that was set when
the drive was commissioned (e.g. p1082).
Description: Display and connector output for the actual converter switching frequency.
Index: [0] = Actual
[1] = Modulator minimum value
Note: The selected pulse frequency (p1800) may be reduced if the drive converter has an overload condition (p0290).
Description: Sets the modulator mode.
Value: 0: Automatic changeover SVM/FLB
2: Space vector modulation (SVM)
3: SVM without overcontrol
4: SVM/FLB without overcontrol
10: SVM/FLB with modulation depth reduction
Dependency: If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without
overcontrol can be selected as modulation type (p1802 = 3).
Refer to: p0230, p0500
Note: When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2, 10), the modulation depth
must be limited using p1803 (default, p1803 < 100 %). The higher the overmodulation, the greater the current ripple
and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
Description: Defines the maximum modulation depth.
Dependency: Refer to: p0500
Note: p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
r1801[0...1] CO: Pulse frequency / Pulse frequency
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [kHz] - [kHz] - [kHz]
p1802[0...n] Modulator mode / Modulator mode
Access level: 4 Calculated: p0340 = 1,3,5 Data type: Integer16
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 10 0
p1803[0...n] Maximum modulation depth / Modulat depth max
Access level: 4 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Units group: - Unit selection: - Func. diagram: 6723
Min Max Factory setting
20.0 [%] 150.0 [%] 106.0 [%]