2 Parameters
2.2 List of parameters
SINAMICS G120C
208 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Display and BICO output for the third status word of the monitoring functions.
Note: Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit is not reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
Description: Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
Description: Sets the value for fixed value 1 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Sets the value for fixed value 2 of the technology controller.
Dependency: Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 2537
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010
04 Speed setp - act val deviation in tolerance
t_on
Yes No 8011
05 Ramp-up/ramp-down completed Yes No 8011
11 Torque utilization < torque threshold value 2 Yes No 8012
p2200[0...n] BI: Technology controller enable / Tec_ctrl enable
Access level: 2 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: CDS, p0170
Units group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2201[0...n] CO: Technology controller fixed value 1 / Tec_ctrl fix val1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950, 7951
Min Max Factory setting
-200.00 [%] 200.00 [%] 10.00 [%]
p2202[0...n] CO: Technology controller fixed value 2 / Tec_ctr fix val 2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Units group: 9_1 Unit selection: p0595 Func. diagram: 7950, 7951
Min Max Factory setting
-200.00 [%] 200.00 [%] 20.00 [%]