2 Parameters
2.2 List of parameters
SINAMICS G120C
244 List Manual (LH13), 04/2014, A5E33840768B AA
Note: KHP: Know-How Protection
- The OEM may only change this parameter for the use case "Sending encrypted SINAMICS data".
- SINAMICS only evaluates this parameter when powering up from the encrypted "Load into file system..." output or
when powering up from the encrypted PS files. The evaluation is only made when know-how protection and memory
card copy protection have been activated.
Description: Displays the status for the write protection and know-how protection.
Dependency: Refer to: p7761, p7765, p7766, p7767, p7768
Note: KHP: Know-How Protection
Re bit 00:
Write protection can be activated/deactivated via p7761 on the Control Unit.
Re bit 01:
The know-how protection can be activated by entering a password (p7766 ... p7768).
Re bit 02:
If it has already been activated, know-how protection can be temporarily deactivated by entering the valid password
in p7766. In this case, bit 1 = 0 and bit 2 = 1 offset.
Re bit 03:
Know-how protection cannot be deactivated, as p7766 is not entered in the OEM exception list (only the factory
setting is possible). This bit is only set if know-how protection is active (bit 1 = 1) and p7766 has not been entered in
the OEM exception list.
Re bit 04:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards/Control Units. This bit is only set if know-how
protection is active and p7765 bit 00 is set.
Re bit 05:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards. This bit is only set if know-how protection is
active and in p7765 bit 01 is set and not bit 00.
Re bit 06:
When know-how protection is activated, the drive data can be traced using the device trace function. This bit is only
set if know-how protection is active and in p7765.2 is set.
Description: Setting for activating/de-activating the write protection for adjustable parameters.
Value: 0: Deactivate write protection
1: Activate write protection
Dependency: Refer to: r7760
r7760 Write protection/know-how protection status / Wr_prot/KHP stat
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Write protection active Yes No -
01 Know-how protection active Yes No -
02 Know-how protection temporarily withdrawn Yes No -
03 Know-how protection cannot be deactivated Yes No -
04 Extended copy protection is active Yes No -
05 Basic copy protection is active Yes No -
06 Trace and measuring functions for
diagnostic purposes active
Yes No -
p7761 Write protection / Write protection
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0