User Manual - Page 178

For G120C.

Loading ...
Loading ...
Loading ...
2 Parameters
2.2 List of parameters
SINAMICS G120C
178 List Manual (LH13), 04/2014, A5E33840768B AA
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
Description: Sets the number of 16-bit words in the PKW part of the USS telegram for the field bus interface.
Value: 0: PKW 0 words
3: PKW 3 words
4: PKW 4 words
127: PKW variable
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
Description: Sets the time values for the fieldbus interface.
The following applies for MODBUS:
p2024[0]: Maximum permissible telegram processing time of the MODBUS slave in which a reply is sent back to the
MODBUS master.
p2024[1]: Not relevant.
p2024[2]: Telegram pause time (pause time between two telegrams).
Index: [0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency: Refer to: p2020, p2030
Note: Re p2024[2] (MODBUS):
If the field bus baud rate is changed (p2020), the default time setting is restored.
The default setting corresponds to a time of 3.5 characters (dependent on the baud rate that has been set).
Description: Displays the receive errors on the field bus interface (RS485).
Index: [0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2023 Field bus int USS PKW no. / Field bus USS PKW
G120C_USS Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 127 127
p2024[0...2] Fieldbus interface times / Fieldbus times
G120C_USS Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
0 [ms] 10000 [ms] [0] 1000 [ms]
[1] 0 [ms]
[2] 0 [ms]
r2029[0...7] Field bus int error statistics / Field bus error
G120C_USS Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: 9310
Min Max Factory setting
- - -
Loading ...
Loading ...
Loading ...