2 Parameters
2.2 List of parameters
Value: 0: No function
1: Reserved
2: Save and activate configuration
3: Delete configuration
Notice: When the DHCP mode is active (p8924 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note: Re p8925 = 2:
The interface configuration (p8920 and following) is saved and activated after the next POWER ON.
Re p8925 = 3:
The factory setting of the interface configuration is loaded after the next POWER ON.
Description: Sets the number of remote controllers expected for PROFINET onboard.
The "Shared Device" functionality is activated with a value = 2.
The drive is being accessed by two PROFINET controllers simultaneously:
- automation controller (SIMOTION or SIMATIC A-CPU).
- safety controller (SIMATIC F-CPU).
Value: 1: Automation or Safety
2: Automation and Safety
Notice: The F CPU may only use PROFIsafe telegrams.
Note: A change only becomes effective after POWER ON, reset or download.
Description: Displays the active station name for the onboard PROFINET interface on the Control Unit.
Description: Displays the active IP address for the onboard PROFINET interface on the Control Unit.
Description: Displays the active default gateway for the onboard PROFINET interface on the Control Unit.
p8929 PN remote controller number / PN rem ctrl num
G120C_PN Access level: 3 Calculated: - Data type: Integer16
Can be changed: C Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 2 1
r8930[0...239] PN Name of Station active / PN Name Stat act
G120C_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
r8931[0...3] PN IP Address of Station active / PN IP of Stat act
G120C_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -
r8932[0...3] PN Default Gateway of Station active / PN Def Gateway act
G120C_PN Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dyn. index: -
Units group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 255 -