2 Parameters
2.2 List of parameters
SINAMICS G120C
70 List Manual (LH13), 04/2014, A5E33840768B AA
Description: Sets the alarm threshold for monitoring the motor temperature for motor temperature model 2 or KTY.
After the alarm threshold is exceeded, alarm A07910 is output and timer (p0606) is started.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency: Refer to: p0612
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Sets the threshold for monitoring the motor temperature for motor temperature model 1/2 or KTY.
Motor temperature model 1 (p0612.0 = 1): alarm threshold
- Alarm A07012 is output after the alarm threshold is exceeded.
Motor temperature model 2 (p0612.1 = 1) or KTY: fault threshold
- Fault F07011 is output after the fault threshold is exceeded.
Dependency: Refer to: p0611, p0612
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Motor temperature model 1:
p0605 also defines the target temperature of the model for r0034 = 100 %. Therefore, p0605 has no influence on the
time up to alarm A07012 being issued. The time is only determined by time constant p0611, the actual current and
the reference value p0305.
Note: The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Sets the system response when the motor temperature reaches the alarm threshold.
Value: 0: No response only alarm no reduction of I_max
1: Messages, reduction of I_max
2: Messages, no reduction of I_max
12: Messages, no reduction of I_max, temperature storage
Dependency: Refer to: p0601, p0604, p0605, p0614, p0615
Note: The I_max reduction is not executed for PTC (p0601 = 1) or bimetallic NC contact (p0601 = 4).
The I_max reduction results in a lower output frequency.
p0604[0...n] Mot_temp_mod 2/KTY alarm threshold / Mod 2/KTY A thresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016
Min Max Factory setting
0.0 [°C] 240.0 [°C] 130.0 [°C]
p0605[0...n] Mot_temp_mod 1/2 threshold / Mod 1/2 threshold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Dyn. index: MDS
Units group: 21_1 Unit selection: p0505 Func. diagram: 8016, 8017
Min Max Factory setting
0.0 [°C] 240.0 [°C] 145.0 [°C]
p0610[0...n] Motor overtemperature response / Mot temp response
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(3), T Scaling: - Dyn. index: MDS
Units group: - Unit selection: - Func. diagram: 8016, 8017
Min Max Factory setting
0 12 12