User Manual - Page 314

For G120C.

Loading ...
Loading ...
Loading ...
2 Parameters
2.6 Quick commissioning (p0010 = 1)
SINAMICS G120C
314 List Manual (LH13), 04/2014, A5E33840768B AA
2.6 Quick commissioning (p0010 = 1)
The parameters required for the quick commissioning (p0010 = 1) are shown in the following
table:
.
Table 2-7 Quick commissioning (p0010 = 1)
Par. no. Name Access level Changeable
p0010 Drive, commissioning parameter filter 1 C(1)T
p0015 Macro drive unit 1 C(1)
p0100 IEC/NEMA motor standard 1 C(1)
p0205 Power unit application 1 C(1,2)
p0230 Drive filter type, motor side 1 C(1,2)
p0300 Motor type selection 2 C(1,3)
p0301 Motor code number selection 2 C(1,3)
p0304 Rated motor voltage 1 C(1,3)
p0305 Rated motor current 1 C(1,3)
p0306 Number of motors connected in parallel 1 C(1,3)
p0307 Rated motor power 1 C(1,3)
p0308 Rated motor power factor 1 C(1,3)
p0309 Rated motor efficiency 1 C(1,3)
p0310 Rated motor frequency 1 C(1,3)
p0311 Rated motor speed 1 C(1,3)
p0316 Motor torque constant 4 C(1,3)UT
p0322 Maximum motor speed 1 C(1,3)
p0323 Maximum motor current 1 C(1,3)
p0335 Motor cooling type 2 C(1,3)T
p0500 Technology application 2 G120C CAN
G120C DP
G120C USS/MB
G120C PN
C(1,5)T
p0500 Technology application 4 G120C PN C(1,5)T
p0640 Current limit 2 C(1,3)UT
p0922 PROFIdrive telegram selection 1 C(1)T
p0970 Reset drive parameters 1 C(1,30)
p1080 Minimum speed 1 C(1)T
p1082 Maximum speed 1 C(1)T
p1120 Ramp-function generator ramp-up time 1 C(1)UT
p1121 Ramp-function generator ramp-down time 1 C(1)UT
p1135 OFF3 ramp-down time 2 C(1)UT
p1300 Open-loop/closed-loop control operating mode 2 C(1)T