Remote Control Commands
R&S
®
NGL200/NGM200
157User Manual 1178.8736.02 ─ 09
See "operation modes" in Figure 6-18.
Parameters:
<arg0> OUT1 | OUTP1 | OUTPut1 | OUT2 | OUTP2 | OUTPut2 | ANY
OUT1 | OUTP1 | OUTPut1
Ch1 is selected as the device channel for digital output fault
source.
OUT2 | OUTP2 | OUTPut2
Ch2 is selected as the device channel for digital output fault
source.
ANY
Any of the available channel which meets the condition sets as
the digital output fault source.
Example:
DIO:FAUL:CHAN 1
Sets channel 1 as the output fault source.
DIO:FAULt:SOURce <arg0>
DIO:FAULt:SOURce?
Sets or queries the "operation modes" of the digital output fault source
See "operation modes" in
Figure 6-18.
Parameters:
<arg0> CC | CV | CR | SINK | PROTection | OUTPut
If "OUTPut" is selected, the "fault output" will be active if the out-
put of the selected channel is off.
Example:
DIO:FAUL:SOUR PROT
Sets the "operation modes" of the digital output fault source as
protection. If any of the protection modes (OCP, OCP, PPP, OTP
and Sense) of the digital output fault source is active, a trigger
event is triggered to the trigger-out signals on the instrument.
DIO:FAULt[:STATe] <arg0>
DIO:FAULt[:STATe]?
Sets or queries the digital output fault.
See "operation modes" in Figure 6-18
Parameters:
<arg0> 1
Enables digital output fault.
0
Disables digital output fault.
Example:
DIO:FAUL 1
Enables the digital output fault.
Advanced Operating Commands